Pharmaceutical ETP

In short: a pharmaceutical ETP treats process effluent that can carry residues of active ingredients, solvents and chemicals, with swings in pH and strength from batch production. A typical plant separates strong and weak streams, equalises and neutralises them, then uses physico-chemical and biological treatment and filtration for discharge or reuse. The design must match your effluent analysis and the limits in your SPCB consent.

✓ Stream segregation✓ Physico-chemical + biological✓ Built around your consent conditions
Pharmaceutical Wastewater Treatment Plant
Global Pharma: 20 KLD ETP and 6 KLD STP by HECS
20 KLD

Pharma ETP for Global Pharma

6 KLD

Hybrid MBBR STP on the same site

FRP

Prefabricated treatment modules

1 MLD

ETP delivered for ONGC

Why pharma effluent needs its own design

  • Batch discharges: flow and strength change through the day as batches start, finish and wash down
  • High, variable COD with solvents and residues of active ingredients
  • pH swings from acid and alkali washes
  • High dissolved solids (TDS) in some streams, which biological treatment does not remove
  • Domestic sewage from canteens and toilets, which is better treated in a separate STP
40 KLD Packaged ETP Installation
40 KLD packaged ETP installation by HECS

Typical treatment stages

StageWhat it does
Stream segregationKeeps strong or high-TDS streams apart from low-strength wash water so each is treated the right way
Collection and equalisationEvens out flow and strength from batch production
NeutralisationBrings pH into the range the next stages need
Physico-chemical treatmentCoagulation, flocculation and settling remove suspended solids and part of the COD
Biological treatmentBacteria break down biodegradable organics; MBBR or MBR are common in packaged plants
Tertiary treatmentFiltration and, where needed, adsorption to polish the water for discharge or reuse
Sludge handlingThickening and dewatering; ETP sludge is often classed as hazardous waste

High-TDS streams may need evaporation or zero liquid discharge (ZLD) where the consent requires it.

1 MLD Effluent Treatment Plant
1 MLD effluent treatment plant by HECS for ONGC

What we need to design your ETP

  • Effluent analysis from a recognised laboratory: pH, COD, BOD, TSS, TDS, oil and grease, and any parameter named in your consent
  • Daily volume and peak flow for each stream, and the production pattern
  • Discharge route: sewer or CETP, surface water, or reuse
  • Your State Pollution Control Board consent conditions
  • Space available and any existing treatment units

Case: 20 KLD ETP and 6 KLD STP for Global Pharma

Global Pharma had two streams: industrial effluent from API processes carrying pharmaceutical residues, solvents and chemicals, and domestic sewage. HECS supplied a 20 KLD industrial effluent treatment plant and a 6 KLD hybrid MBBR sewage treatment plant, built in FRP prefabricated modules for a corrosive environment, with automated sensors and controls for stable operation. The client now reuses a significant portion of the treated water. Read the full case study.

Pharmaceutical Wastewater Treatment Plant
Global Pharma: ETP and STP in FRP prefabricated modules
FAQs

Pharmaceutical ETP: FAQs

Can’t find your answer? Ask an HECS engineer. We reply within minutes.

An effluent treatment plant designed for wastewater from pharmaceutical manufacturing, which can contain residues of active ingredients, solvents and chemicals and varies with batch production.

Domestic sewage is usually treated in a separate STP. Process effluent needs its own treatment, designed from the effluent analysis.

MBBR handles load swings well; MBR gives finer filtration where water is reused. The right choice depends on the effluent analysis and discharge route.

ETP sludge is often classed as hazardous waste and must be stored and disposed of as your consent and the Hazardous Waste Rules require.

Your effluent analysis, daily volume and peak flow for each stream, discharge route, consent conditions and the space available.

Only where the consent or local rules require it. Check your State Pollution Control Board consent conditions.

Discuss your pharma ETP

Share your effluent analysis, daily volume, discharge route and consent conditions, and we will propose a treatment scheme.

Pharmaceutical Effluent Treatment Plant (ETP)